Improvement of Power System Stability by using SVC with Cascade PID Controller

Table of contents

1. Introduction

he challenge facing power system engineers today is to use the existing transmission facilities to greater effect [1] . Power system should retain its synchronism during and after all these kind of disturbances. Therefore the transient stability is an important security in power system design. So FACTS has come to help the power system engineer [2][3] . The SVC is one of the important FACTS devices whose effectiveness for voltage control is well known. The AC power transmission system has diverse limits, classified as static limits and dynamic limits [4][5] .Traditionally, fixed or mechanically switched shunt and series capacitors, reactors and synchronous generators were being used to enhance same types of stability augmentation [6] . For Authors ? ? ?: Department of EEE, Rajshahi University of Engineering & Technology Rajshahi-6204, Bangladesh. e-mails: [email protected], [email protected], [email protected] many reasons desired perfor-mance was being unable to achieve effectively. A static VAR compensator (SVC) power compensation on high voltage transmission networks and it can contribute to improve the voltage profiles in the transient state and therefore, it can improve the qualities and performances of the electric services [6] . An SVC can be controlled externally by using properly designed different types of controllers which can improve voltage stability of a large scale power system [7] . However, in this study, With a view to get better performance, A new PID has been designed & proposed for SVC to injects V qref externally for the improvement of power system stability. The dynamic nature of the SVC lies in the use of thyristor devices (e.g. GTO, IGCT) [6] . Therefore, thyristor based SVC with PID controllers has been used to improve the performance of 2-machine power system.

2. II.

3. Control Concept of SVC

An SVC is a controlled shunt susceptance(B) which inject reactive power (Q net ) into thereby increasing the bus voltage back to its net desired voltage level. If bus voltage increases, the SVC will inject less (or TCR will absorb more) reactive power, and the result will be to achieve the desired bus voltage[Fig. 1]. Here, +Q cap is a fixed capacitance value, therefore the magnitude of reactive power injected into the system, Q net , is controlled by the magnitude of -Q ind reactive power absorbed by the TCR. The basis of the thyristor controlled reactor (TCR) which conduct on alternate half-cycles of the supply frequency. If the thyristors are gated into conduction precisely at the peaks of the supply voltage, full conduction results in the reactor, and the current is the same as though the thyristor controller were short circuited. SVC based control system is shown in Fig. 1 [6] . for secondary loop controller. Cascade control is mainly used to achieve fast rejection of disturbance before it propagates to the other parts of the plant.PID controller in cascade architecture is the best choice compared to conventional single loop control system for controlling nonlinear processs.

4. III. SVC V-I characteristics

In voltage regulation mode (the voltage is regulated within limits as explained below). b). In VAR control mode (the SVC susceptance is kept constant). From V-I curve of SVC, From Fig. 2 [3], V=V ref +X s .I,: In regulation range(-Bc max <B<Bc max ) V=I/Bc max , , : SVC is fully Capacitive(B=Bc max ) V=1/Bl max , : SVC is fully inductive(B=Bl max )

5. Power System Model

This example described in this section illustrates modelling of a simple transmission system containing 2-hydraulic power plants[Fig. 3]. SVC has been used to improve transient stability and power system oscillations damping. The phasor simulation method can be used. A single line diagram represents a simple 500 kV transmission system is shown in Fig. 3[ 9]. Another machine is swing generator.PID is used in the model to add damping to the rotor oscillations of the synchronous machine by controlling its excitation current [5] . Any disturbances that occur in power systems due to fault, can result in inducing electromechanical oscillations of the electrical generators. Such oscillating swings must be effectively damped to maintain the system stability and reduce the risk of stepping out of synchronism.

V.

6. Simulation Results

The load flow solution of the above system is calculated and the simulation results are shown below. Two types of faults: A. single line to ground fault & B. Three phase fault have been considered.

Consider a 1-phase fault occurred at 0.1s & circuit breaker is opened at 0.2s (4-cycle fault), Without SVC, the system voltage, power & machines oscillates goes on unstable[Fig. (5,7,9)]. But if SVC(without controller) is applied then voltage becomes stable within 3s [Fig. 6], power becomes within 3s[Fig. 8] & machines oscillation becomes stable within 4.5s [Fig. 10]. All results has been summarized in table-III

7. Designe of Cascade Propotional Integral Differtional Controller (PID)

The Tyreus-Luyben procedure is quite similar to the Ziegler-Nichols method but the final controller settings are different. Tyreus-Luyben PID Controller, the values of delay time, rise time, and settling time are better in comparison with Modified Ziegler-Nichols method. Also this method only proposes settings for PI and PID controllers. These settings that are based on ultimate gain and period are given in table 1. For some control loops the measure of oscillation, provide by ¼ decay ratio and the corresponding large overshoots for set point changes are undesirable therefore more conservative methods are often preferable such as modified Z-N settings In this method, the parameter is selected as T i =?,T d =0. Using the proportional controller Action

dt t de T K dt t e T K e(t) K t u d p i p p ) ( ) ( ) ( ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? S S d i p T T 1 1 K E(s) U(s) K p =0.2K cr , T i =0.5P cr , T d =0.33P cr

Notice that the PID controller tuned by proposed Ziegler-Nichols tuning methods rules as follows,

8. Simulation Results

The network remains same [

9. Results & Discussions

The performance of the proposed PID Controller with SVC has been summarized in the table -III. In table-III, ? (infinite time) means the system is unstable, SVC rating in MVA. The network is simulated in three steps; without SVC, With SVC, SVC with proposed CASCADE PID Controller.

10. Conclusion

The obtained results of the conducted investigations along with the associated simulation demonstrated clearly that the proposed (desinged) cascade PID controller enhanced significantly the effectiveness of the integrated SVC in the examined power controller because of shorter stability time, simple designed system. In cascade PID Controller may be highly suitable as a SVC, low cost & highly efficient controller. The proposed cascade PID for SVC is proved to be very effective of robust power system within very shortest possible time for both steady state & dynamic conditions. These proposed cascade PID Controller can be applied for any interconnected multi-machine power system network for stability improvement.

These controller can be applied to another FACTS devices namely SSSC, STATCOM, UPFC whose controllers may be controlled externally by designing different types of controllers which also may be tuned by using different algorithm i.e. Fazzy logic,ANN, Genetic algorithm, FSO etc. for both transient and steady state stability improvement of a power system.

11. References Références Referencias

Figure 1. Figure 1 :
1Figure 1 : SVC based control system
Figure 2. Figure 2 :
2Figure 2 : Steady state(V-I) characteristic of a SVC IV.
Figure 3. Figure 3 :YearFigure 4 :
34Figure 3 : Single line diagram of 2-machine power system A 1000 MW hydraulic generation plant (M1) is connected to a load centre through a long 500 kV, total 700km transmission line. A 5000 MW of resistive load is modelled as the load centre. The remote 1000 MVA plant and a local generation of 5000 MVA (plant M2) feed the load. A load flow has been performed on this system with plant M1 generating 950 MW so that plant M2 produces4046 MW. The line carries 944 MW which isclose to its surge impedance loading (SIL = 977 MW).To maintain system stability after faults, the Transmissi online is shunt compensated at its centre by a 200MVAR Static VAR Compensator (SVC).
Figure 4. Figure 5 :Figure 6 :Figure 7 :Figure 8 :Figure 9 :Figure 10 :Figure 11 :
567891011Figure 5 : Bus voltages in p.u for 1-phase fault(without SVC)
Figure 5. Figure 13 :
13Figure 13 : PID controller is in proportional action
Figure 6. Fig. 14 ]
14only increase K p from 0 to a critical value K cr . At which the output first exhibits sustained oscillations[Fig.14]. Thus the critical gain K cr & the corresponding period P cr are experimentally determined. It is suggested that the values of the parameters K p T i T d should set according to the following formula .
Figure 7. Figure 15 :
15Figure 15 : Internal Structure of cascade PID controller with d? input
Figure 8. Fig. 4 ]
4,just simple SVC is replaced by cascade PID controlled SVC. During fault ,machines speed deviation(d?) always monitored by cascade PID controller & taking input of this oscillation, after processing this signal reaches as Vref in SVC . it reduces damping of power system oscillation& helps SVC to improve stability. Two types of faults has been considered: A. Single line to ground fault and B. Three phase L-L fault During 1-phase faults, if cascade PID is used with SVC controller then, the system voltage becomes stable within 1.5s with 0% damping [Fig.16] &Power (P,Q) becomes stable within 1.2s& 1s [Fig.17
Figure 9.
,18] & Machine speed deviationt d? becomes stable at 2.8s[Fig.19].
Figure 10. Figure 16 :
16Figure 16 : Bus voltage in p.u for 1-Ø fault (with cascade PID)
Figure 11. Figure 20 :
20Figure 20 : Bus voltages in p.u for L-L fault (with cascade PID)
Figure 12. s
1. [S Punnepalli , G. Srinivasulu Reddy , "Effective Way to Damping Power Oscillations Using Static Var Compensator With Fuzzy logic controller ",IJTPE: V ol. 4, No. 4, pp. 89-94, Dec. 2012. 2. P. Kundur, "Power System Stability and Control" , McGraw Hill, New York, 1994. Improvement of Power System Stability By Using SVC With Cascade PID Controller
Figure 13. Table 1 :
1
Controller Kp Ti Td
PI Kcr/3.2 2.2Pcr
PID Kcr/3.2 2.2Pcr Pcr/6.3
Figure 14. Table 2 :
2
Controller Kp Ti Td
PI 0.2Kcr Pcr/2
PID 0.2Kcr Pcr/2 Pcr/3
PID controller is tuned by the proposed both
Tyreus-Luyben tuning and modified Ziegler-Nichols
methods. The PID controller has three term control
signal
Figure 15. Table 3 :
3
1
2

Appendix A

  1. Bus power, P in MW for L-L fault, 21. (with cascade PID)
  2. Transient stability Enhancement of multi machine using Global deviation PSS. Ali M Yousef . Journal of Engineering sciences April 2004. 32 (2) p. . Faculty of Engineering, Assiut University
  3. Modeling and Simulation of Static VAR Compensator for Improvement of Voltage Stability in Power System, Amit Garg . 2.
  4. Power System Stability Improvement By Using SVC With PID Controller. Dr Habibur , Harun Fayzur . IJETAE 2250-2459. July 2012. 2 (7) .
  5. Power System Stability Improvement By Using SVC With TID Tuned PID Controller, Dr Habibur , Harun Fayzur . October-2012. India. 1 p. . IJARCET
  6. MATLAB Math Library User's Guide, Math Works. Inc.
  7. A Robust Control for Shunt and Series Reactive Compensators to Damp Electro Strategy mechanical Oscillations. T Athay , R Podmore , S Virmani . IEEE Transactions on Power Delivery Oct. 2001. 16 (4) p. .
Notes
1
© 2013 Global Journals Inc. (US)
2
© 2013 Global Journals Inc. (US) a) Designed of PID Controller
Date: 2013-01-15